Lite Evac HP Refrigerant Recovery Equipment
Item #: LRH Lite Evac Recovery Unit
RefTec’s Stand up Lite Evac™ (Dorin) Recovery/ Recycle/Reclaim system provides efficient and safe recovery of most high pressure refrigerants. Make sure you have a recovery tank with a minimum 3/4″ male flare vapor port and a minimum 3/4″ male flare liquid port, or larger ports if possible. This tank or series of tanks must be able to hold the entire refrigerant charge at 80% full and also must be pressure rated for the specific refrigerant being recovered.
High Speed, High Efficiency Recovery of all High Pressure Refrigerants
- Fast and portable unit for high pressure refrigerants
- Unit is mounted in a solid lightweight aluminum frame
- For use with medium-large tonnage chillers
- 2 Hard rubber tires for easy portability
- R410a rated
- Lightweight commercial unit at only 161lbs
- 80% tank full float switch and 12’ cable
- Air cooled unit
- ETL certified
Specifications
Push/Pull Rates
(R22) 81-lbs/min
R410a 65-lbs/min
Vapor Rates (R22)
(R22) 2.14-lbs/min
(R410a) 1.75-lbs/min
Dimensions (lxwxh in inches)
Hand Truck Model:24″x23″x38″
Float Connection
3-pin BH
Connections
1/2” flare
Low Pressure Switch
15″ Hg
Liquid and Vapor Ports
1/2” Threaded Connect
Certifications Certified by ETL to UL-1963 standards | Rated in accordance with ARI Standard 740-1998
- Specifications: 115V/60HZ/1PH/20A,110V/50HZ/1PH/20A
- Specifications: 230V/60HZ/1PH/20A,220V/50HZ/1PH/20A
Included with purchase:
- 2- 30cu. Inch Filter Driers
- 80% Tank Float Cable (12ft)
- 50ft. Power Cord
Optional Accessories
- 050-010-LRH Hose Kit consisting of (2) 10’ and (1) 20’ hoses, all ½” diameter
- LRH-WCK External water cooled condensing kit with hoses