Allvac Universal Refrigerant Recovery Unit
Item #: ARH Allvac Universal Refrigerant Recovery Unit
Universal High & Low Pressure Recovery
Combines capabilities of Evac Commercial & Lovac systems to offer great recovery rates on R11, R12, R22, R113, R123, R134a, R404, R500, R502, R410a & other high pressure refrigerants or blends. Rugged open drive compressor provides years of reliable service, even on refrigerants heavily contaminated with oil, air, moisture, & acids. Switching between refrigerants simply involves oil & filter changes along with evacuation of the unit. Air/water cooled option incorporates a water cooled plate exchanger in line with the air cooled condenser. This model may operate with or without condensing water.
Specifications
Push/Pull Rates (R22)
325-lbs/min
Vapor Rates (R22)
6.0-lbs/min
Push/Pull Rates (R11)
100-lbs/min
Vapor Rates (R11)
0.66-lbs/min
Connections
¾” flare
Dimensions
Inches: l x w x h: 22″ x 24″ x 44″ Dimensions shipping 48″ x 40″ x 51″
Float Connection
3-pin BH
Low Pressure Switch
15″ Hg or 29″ Hg
Product Numbers
- Specifications: 220-240V,50/60Hz,3Ph,3Hp,20A
Weight: 340lbs - Condensor: Air Cooled
- Specifications: 220-240V,50/60Hz,1Ph,3Hp,30A
Weight: 340lbs - Condensor: Air Cooled
- Specifications: 415-460V,50/60Hz,3Ph,3Hp,15A
- Weight: 340lbs
- Condensor: Air Cooled
- Specifications: 240/460V 50/60Hz,1PH,3Hp,30A
Weight: 375lbs - Condensor: Air Cooled
- Specifications: 220-240V,50/60Hz,3Ph,3Hp,20A
- Weight: 345lbs
- Condensor: Air/Water Cooled
- Specifications: 220-240V,50/60Hz,1Ph,3Hp,30A
Weight: 345lbs - Condensor: Air/Water Cooled
- Specifications: 415-460V,50/60Hz,3Ph,3Hp,15A
- Weight: 345lbs
- Condensor: Air/Water Cooled
- Specifications: 240/460V,50/60Hz,1Ph,3Hp,30A
- Weight: 380lbs
- Condensor: Air/Water Cooled
Included With Purchase
- One 48-cubic inch drier core 50-ft power cord for controls
- 12-ft tank float cable 50-ft power cord for recovery unit
- (2) 3/4″-5/8″ & 5/8-1/2″ fittings Two ¾” x 10ft & One ¾” x 20ft recovery hoses w/ ball valves